SLC to Modem Configuration
BY Steven Eckwielen, October 1997
This is the setup information for connecting a modem to a Allen-Bradley SLC 500. We have tested this setup with a 14,400 and a 57k USRobotics modem. The Modem to SLC cable is a standard off the shelf 25-to-9 pin serial cable.
|
USRobotics Modem DIP Settings
|
|
SLC Communications Setup
|
|
1
|
DN
|
DTR Override
|
|
Computer/Terminal Address
|
7
|
|
2
|
UP
|
Verbal Result Codes
|
|
HW Type
|
S/03,S/04,CH0,1770-KF3,1747-K3
|
|
3
|
DN
|
Display Result Codes
|
|
Online Wait for Reply Timeout
|
15 seconds
|
|
4
|
UP
|
Echo Offline Command
|
|
Communication Port
|
COM1
|
|
5
|
UP
|
Auto Answer
|
|
Baud
|
9600
|
|
6
|
UP
|
Carrier Detect Normal
|
|
Parity
|
None
|
|
7
|
DN
|
Load Factory Settings
|
|
Error Checking Mode
|
CRC
|
|
8
|
UP
|
Dumb Mode
|
|
Protocol
|
Full Duplex
|
|
|
|
Dial
|
Yes
|
|
|
|
|
|
CH0 Sys
|
|

|
|
Communication Driver
|
DF1 Full Duplex
|
|
Baud Rate
|
9600
|
|
Stop Bits
|
1
|
|
Duplicate Packet Detection
|
Enabled
|
|
ACK Timeout (x20ms)
|
50
|
|
Control Line
|
No Handshaking
|
|
Source ID
|
9
|
|
Parity
|
None
|
|
Error Detection
|
CRC
|
|
Max Retries
|
3
|
|
ENQ Retries
|
3
|
|
Embedded Response
|
Enabled
|
|
|
|
|
|
|
|
© Birket Engineering, 1997
|